Thursday, January 15, 2015

Building an HF Directional Coupler

I previously discussed some of the theory underlying lumped-element (i.e. High Frequency) directional couplers here: http://k6jca.blogspot.com/2015/01/notes-on-directional-couplers-for-hf.html

Now I'm going to build one.

I'm using the Tandem Coupler topology (see previous post).  Here's what the circuit will look like:


Why 16 turns?

I want enough turns on the transformer to present a high impedance on 160 meters, but not so many turns that they effect performance on 6 meters.  So, I want to minimize the number of turns used and try to find a core with a high mu.  But too few turns also means that the terminations on the FWD and REF ports will need to dissipate higher power.

With this in mind, my goal for the Coupling-factor (coupling of Input port to Forward port) is -24 dB, which means 16 turns on a transformer whose primary is a single turn (i.e. 20log(16) = 24).

Note that if the coupling from IN port to FWD port is -24 dB, then the power at the FWD port will be P(in) * 0.004 (i.e 24 dB down).  So if power at the IN port is 100 watts, there will be 0.4 watts at the FWD port (important because the 50 ohm load on this port must be able to dissipate this power).

But what cores to use?  Let's go to the junkbox and see what I can dig up...

Here are some I dug up.  I believe these are primarily used for RFI mitigation applications, but they are made of type-43 material.  Let's see if they'll work. 


Note that they are ferrite, not powdered-iron (link to datasheet is at the end of this post).  Per N8LP's QEX article (see link at end), ferrite cores are more prone to saturation than are powdered-iron cores.  I don't know how much power these cores will tolerate -- I'll have to experiment.  [Update:  more info on applying these cores here: http://k6jca.blogspot.com/2015/07/antenna-auto-tuner-design-part-5.html and here: http://k6jca.blogspot.com/2015/12/antenna-auto-tuner-design-part-8-build.html]

I'll need sufficient inductance at 1.8 MHz to ensure that the voltage-sense transformer presents a high impedance compared to 50 ohms.  I wound test coils on two of these cores, each with 16 turns of wire, and then I measured their inductance (these are not the coils I'm actually building the coupler with).  They were 1.1mH and 0.7mH, respectively (measured on GenRad 1657 Digibridge, at 1 KHz).  I don't know why there's a difference in inductance, but I suspect it's due to a variation in the ferrite core mu.

Another important Directional Coupler parameter is Directivity.  Here, Directivity is defined as the coupling from the OUT-to-REF ports minus the coupling from IN-to-REF ports.  Directivity affects SWR accuracy -- poor directivity means that "forward" power is getting into the "reflected" power port and corrupting the reading.  So my goal is to have Directivity be at least -40 dB over the HF range (1-30 MHz, and ideally up to 54 MHz, but I'm also willing to sacrifice a bit at 6 meters if it gets me better performance at 30 MHz and below).

Some notes on construction:

1.  For the "one turn" winding I ran a straight piece of Thermax MIL-C-17 spec RGU-142 coax through each transformer.
  • The Max Power specification of this coax is 2,400 watts at 100 MHz.  Not bad!
  • This coax's max working voltage is 1400 V (not sure if that's a peak V or an RMS spec). Note that for an SWR of 1:1, 100 watts Forward Power into 50 ohms equals 100V peak, on the transmission line (if the SWR were infinite and Forward Power were still 100 watts, this peak voltage becomes 200V).  And at 2000 watts and 1:1 SWR, Peak V is 442 volts.  So at an infinite SWR peak voltage for 2000 watts of forward power would be 884 V, peak. 
2.  The outer sheathing of the coax has been left on, but trimmed back to expose the shield.  The shield is also trimmed back, but left slightly exposed at both ends (and tinned by me) so that I could experiment with which end of the coax shield should be grounded.  Do not ground both ends!

3.  I used insulated wire in lieu of enameled wire for the transformer secondary windings.  Insulation breakdown is especially important for the voltage-sense transformer, whose 16-turn secondary is across the coax.  So, if SWR were infinite and Forward Power were 100 watts, there will be 200V, peak, across the windings of this transformer.

4.  In the box I added a center-divider (made of PCB stock) between the two transformers.  I found through experimentation that this divider should fully contact the three sides of the case in which I was mounting it.  This was a problem because my case is aluminum; I can't solder to it.  So I lined the inside of the case with copper tape and soldered the divider to it.  Note:  all tape seams were soldered along their entire length.

Here's the result.  For my first tests, I'm going to call the lower-left port the IN port, the upper-left port is the OUT port (but this will later change, as you will discover further on...)


In the above image, the FWD port (relative to the IN port) is the lower-right port, and the REF port is the upper-right port.

Measuring and Improving Performance:

Let's make some measurements with a Vector Network Analyzer (VNA).  Here's my test setup with an HP 3577A and matching S-parameter unit.



Directivity will be all important, so I want to see what I can do to minimize the coupling between the IN port and the REF port (because the coupling from OUT-to-REF is fixed at -24 dB).

Before I start experimenting, let's get a baseline.  Here's a plot of Coupling, IN port to REF port, 0.1 - 100 MHz:


Directivity is the coupling shown above reduced by the forward coupling (-24 dB for 16 turns), so it will be 24 dB worse than the image above.

Can I improve Directivity?  Time to experiment (this is where the design becomes more art than science).  Here are some examples of what I tried...

If I move this wire closer to the case (using an insulated stick)...


There's an improvement.  The coupling is lower by about 5 dB at 30 MHz, for example.


So I incorporate this "gimmick" of wire routing.  Now, let's put cover on.  Here's the cover, screwed down.


 Note that the response has worsened.


 But, if I remove just one screw...


...there's an improvement!


Yikes!

This is why there's an art to RF -- it's difficult to simulate these types of effects.

Another example of stray and parasitic effects...as I move a copper plate over the top, touching one side of the case but not both sides of the case...


...performance improves!


But if I continue to move the copper across the case until it's also touching the opposite side (straddling the case)...


...performance worsens by 10 dB at 54 MHz!



Long story short...after spending much time trying to improve performance when the case was screwed on, I finally decided that I wasn't really advancing.  So, it was time to move on to the next step: characterizing the coupler's performance.

But, while making these characterization measurements I discovered that the ports are not quite symmetric in their performance.  Specifically, there's a difference in Directivity, depending upon which port we define to be our "IN" port.

With this new data, I redefined the port configuration to maximize Directivity performance from 1 to 30 MHz.  Here are the new port assignments:


And here's the Directional Coupler's characterization data for this new configuration.:

(click on image to enlarge)

Note that I've assigned the ports so that the Directivity data with the yellow background is appreciably better than the "Reverse Directivity."  This is because, in my applications, I will be applying power to the IN port, and thus I want to minimize any coupling of this power to the REF port.

(I don't know why there is a difference in directivity.  But if I want that additional performance at 54 MHz (about 2.5 dB improvement in Directivity), all I need to do is swap the In and Out connections and swap the FWD and REF connections).


Here's a drawing showing the construction connections in better detail:

(click on image to enlarge)

(Note the "gimmick" of routing one of the wires closer to the wall of the case.)

And some additional pictures...

Voltage-sense transformer on left (connected between REF (top) and FWD (bottom) ports):


Current-sense transformer on right (connected between OUT (top) and IN (bottom) ports):




Plots of the four coupling parameters (1 - 100 MHz)
(click on images to enlarge)

IN-port to FWD-port:


OUT-port to REF-port:


IN-port to REF-port and OUT-port to FWD-port:

Although they ought to be identical (or close to it), this image shows that the IN-port to REF-port coupling is noticeably different from the OUT-port to FWD-port coupling.  Note the difference at 30 MHz and below.  The IN-port to REF-port coupling is significantly lower (what we want!).



A plot showing actual Directivity (I'm measuring IN-to-REF, but after first normalizing the measurement of OUT-to-REF to 0 dB.  That normalization factor is then automatically applied to this new measurement).



For the sake of completeness, here is what the OUT-to-FWD coupling looks like over the range of 0.1 - 200 MHz (the full range of the 3577A Network Analyzer).  (Note that the IN-to-REF plot is about the same).  Horizontal divisions are 20 MHz.  Note that the hump just to the right of the middle of the plot is right around 144 MHz.  Therefore expect very poor performance (because of poor directivity) on 2 meters!



Here's an interesting photo.  This is what happens to the IN-port to REF-port coupling when the coupler's top cover is removed...


Here's the coupler, case screwed on.


Other Measurements

(Note that these were made before I reassigned the ports.  Never the less, they should be close to the values of the reassigned ports).

Let's take a look at S11 in the IN port with all other ports terminated in 50 ohms.  Here's the setup:


First, for reference, look at just S11 of the 50 ohm reference that I will attach to the coupler's "output" port (roughly -65 dB at 54 MHz).


And here's S11 of the terminated coupler.  Roughly -27 dB (apologies for the blurriness) at 54 MHz.


S11 of same configuration on Smith Chart:


S11 with all ports unterminated.  That is, S11 of just the coupler itself.


Measuring Self-Resonant-Frequency (SRF) of the 16-turn coil. Coil is paralleled with 50 ohm load, thus no cables, to minimize the effect of cable capacitance on SRF.  Look for dip in S11.


S11 plot.  And a nice dip at 10 MHz. That's the SRF (I don't know why there is a second dip).


Hmmm...I wonder if performance would improve if the SRF were higher...


Directivity and SWR Uncertainty:

Directivity has a direct effect upon VSWR error -- the poorer Directivity is, the more uncertain will be the VSWR reading (that is, the more uncertain will be the measured Return-Loss).

For example, if Directivity is -40 dB, VSWR uncertainty is fairly small for VSWRs under, say, 5, as shown in the graph below.  That is, if your VSWR measures 5:1 or better, the actual SWR will be close to that value.

Let's say the measured SWR is 3:1.  If our directivity is -40 dB, then the SWR might actually be somewhere between 2.9:1 and 3.1:1 -- in other words, VSWR will be within a narrow range that's essentially equal to 3:1.


But as Directivity worsens, uncertainty grows.  If Directivity = -30 dB, then a measured VSWR of  3:1 could, in reality, be a VSWR anywhere between 2.7:1 and 3.4:1.


Or let's say Directivity is only -20 dB.  Now, if we measure a VSWR of 3:1, the actual VSWR could be anywhere from 2.3:1 to 4.6:1.  And this spread widens significantly for VSWRs greater than 3:1, as seen in the graph below.



And for reference, here's the graph for -35dB Directivity (my Coupler at 54 MHz):



Note:  These graphs were each calculated using an EXCEL calculator, "VSWR Uncertainty versus Directivity, Return-Loss", which can be downloaded via a link in the "Links" section, below.  I'm assuming the equations in the spreadsheet are correct.


Other Notes and Comments:
  1. Ground only one side of each coax cable that runs through the cores, not both sides!
  2. Experiment with which ends of the transformer windings connect to ground and which ends connect to ports.  For example, the Voltage-sense transformer could connect to either the IN port or the OUT port, and also either end of the 16 turns of this transformer could go to this selected port.  These choices do affect performance.  You will need to experiment and discover which connections give the best response.
  3. Experiment with grounding one side or the other of the shields of each of the "one turn" coax cables.
  4. A Network Analyzer has been invaluable.  I don't know how I would have tested this coupler without one.
  5. And many thanks to Dick Benson, W1QG, for his invaluable help and advice!!!

>>> Important Updates!!! <<<


For additional information on designing Direction Couplers, please see this later post:  http://k6jca.blogspot.com/2015/07/antenna-auto-tuner-design-part-5.html .

As part of the Directional Coupler design in this post I analyze core selection (among other things).  Serendipitously, my core choice (above),  Fair-Rite 2643625002, looks pretty good, per my spreadsheet below (see http://k6jca.blogspot.com/2015/07/antenna-auto-tuner-design-part-5.html for more details).

(click on image to enlarge)

(Note that peak voltage and peak current (at peak power, i.e. AM modulation) assume an infinite SWR on the transmission line.)

Also, I describe the build of another Directional Coupler here:  http://k6jca.blogspot.com/2015/12/antenna-auto-tuner-design-part-8-build.html


Links to my Directional Coupler blog posts:

Notes on the Bruene Coupler, Part 2

Notes on the Bruene Coupler, Part 1

Notes on HF Directional Couplers (Tandem Match)

Building an HF Directional Coupler

Notes on the Bird Wattmeter

Notes on the Monimatch

Notes on the Twin-lead "Twin-Lamp" SWR Indicator

Calculating Flux Density in Tandem-Match Transformers


And some related links from my Auto-Tuner and my HF PA posts:

Auto Tuner, Part 5:  Directional Coupler Design

Auto Tuner, Part 6:  Notes on Match Detection

Auto Tuner, Part 8:  The Build, Phase 2 (Integration of Match Detection)

HF PA, Part 5: T/R Switching and Output Directional Coupler


Useful Links:

Directivity and VSWR Measurements
Bird, Straight Talk about Directivity

Mini-circuits, Table, Return Loss vs VSWR
EXCEL Calculator, VSWR Uncertainty versus Directivity, Return-Loss

Fair-rite 2643625002 datasheet
Thermax RGU-142 Coax Datasheet

Philips, Design of HF Wideband Power Transformers, Part 1
Philips, Design of HF Wideband Power Transformers, Part 2

N8LP Wattmeter (QEX Article)
N2PK Power and Return-Loss Meter


And Finally, the Standard Caveat:
I could have easily made a mistake in any of the above, so please approach this material with a bit of skepticism -- don't assume it's correct.  And if you do find an error, or would like more detail, please feel free to contact me.

Thursday, January 1, 2015

Notes on Directional Couplers for HF

Many years ago, when I was a student studying Electrical Engineering, one of my professors mentioned that the Standing-Wave Ratio (SWR) on a transmission line could be calculated by first finding (and measuring) a voltage maximum on a transmission line and then moving 1/4 wavelength away and measuring the voltage there.  If there were a standing wave, there would be a voltage minimum at this point.  And these two values (voltage maxima and minima) could then be used to calculate the standing wave ratio:

SWR = |Vmax| / |Vmin|

And I remember thinking...the inexpensive Radio Shack SWR meter that, as a teenager, I'd been using with my ham radio was only about 5 inches long.  Nowhere near the 20 meters (65 feet) of length required if SWR were to be measured on 80 meters the traditional maxima/minima way.  How did it work?  Something else must be going on inside those meters, but what?

Wait a sec...to measure SWR on 80 meters,
shouldn't these connectors be 65 feet apart?

Many years later, I finally decided to dig a little deeper...

On HF, SWR is measured using "lumped-element" directional couplers.  By "lumped-element" I mean that the components of the coupler and their interconnections are all much much shorter than the wavelengths of the frequencies being measured.

There seem to be two main topologies for these lumped-element couplers.  I'll call these two topologies the 1) Tandem  coupler (or bridge), and the 2) Bruene coupler, or bridge (after Warren Bruene, of Collins Radio).

The Tandem coupler topology was popularized for ham radio use by John Grebenkemper in his article, "The Tandem Match -- an Accurate Directional Wattmeter", which appeared in the January, 1987 issue of QST magazine.


(QRPers might recognize this as the "Stockton" bridge, named after David Stockton, G4ZNQ, for his article "A Bi-directional Inline Wattmeter," in the Winter 1989/90 issue of Sprat.)

The Bruene directional coupler is an older design, and it made its first appearance (to my knowledge) in Bruene's article "An Inside Picture of Directional Wattmeters," in the April, 1959 issue of QST.

Here's an example of the Bruene directional coupler:


Being lumped-element couplers, both of these designs operate by sampling the line voltage and line current at a single point (not two points 1/4-lambda apart!).  Both sample the line current with a transformer.  Their difference is how they sample line voltage -- line voltage is sampled with a second transformer in the Tandem coupler, while Bruene uses a capacitive divider to sample this voltage.

In other words, although the two topologies appear different, their fundamental principles of operation are essentially the same.

Let's get a better understanding of how these couplers (or bridges) operate.  I'll focus on the Tandem Coupler:

The "Tandem" Directional Coupler, in a Transmission Line Environment

Before getting into the discussion of the Tandem Coupler in an environment with Forward and Reflected waves, let me make an important point:

The Tandem Coupler, being made of "lumped elements" (in this case, two toroidal transformers and two resistors), is only looking at the voltage and current present at its output port.  It has no idea what the load is, or even how the load is connected to the port.  The load might be a resistor or other component simply clipped onto the output connector with test leads, or it might be a length of transmission line with a load (either known or unknown) at its other end.

Irrespective of what the load is (transmission line, clipped-on component, or whatever), the Tandem Coupler gives us voltage readings that can be interpreted in terms of Forward and Reflected waves.  It is important to remember:  these readings should only be interpreted as representing actual Forward and Reflected waves when the Tandem Coupler is connected in a transmission line with the same characteristic impedance, Zo, as the Tandem Coupler's designed-for target impedance!

Therefore, for this discussion I will assume that the Directional Coupler is inserted into a transmission line of the designed-for (target) characteristic impedance.

 Tandem Directional Coupler (W1QG)

Let's consider a transmission line with two independent signals on it.  One signal (let's call it the Forward signal) is traveling left-to-right on the line, while other signal (let's call it the Reflected signal) is traveling right-to-left.

These signals have voltage amplitudes of Vfwd and Vref, and, because they are independent of one another, their currents Ifwd and Iref are simply the signal voltages divided by the characteristic impedance of the transmission line.  That is:

Ifwd = Vfwd/Zo
and
Iref = Vref/Zo


From the Principle of Superposition, we know that V at any point on the transmission line is simply Vfwd+Vref.  And the total current at any point on the line, I, is equal to Ifwd - Iref (they subtract because the currents flow in opposite directions).

So now let's insert the tandem coupler into the transmission line at that point, as shown in the drawing below.  Note that I'm simplifying the drawing and not including source or load impedances (at either end of the transmission line) for this analysis.   


So what's going on inside the directional coupler?

First, note that the total current, I, flows through L1.  Therefore the current through L2 is I/N, or (Ifwd-Iref)/N, where N is  the turns ratio.

Similarly, the total voltage across L3 is V.  Therefore, the voltage across L4 is V/N, or (Vfwd+Vref)/N.

To see this, first let's define the orientations of the primary and secondary voltages and currents in each transformer, given the "polarity dots" of their windings:


Next, let's assign values to these voltages and currents based upon the transmission line's forward and reflected voltages and currents:


The measurement ports for this device are across R3 and R4.  So let's calculate the voltages across these two resistors.

For simplification of the calculations, I am going to assume the following:
  1. The voltage drop across L1 is negligible.
  2. The current through L3 is negligible.  
To demonstrate how this coupler works, I am going to assume that the two transformers are ideal transformers.  Also, I would like to use the Principle of Superposition to calculate the voltages across R3 and R4.  But to use this technique, I need to somehow model the transformers as independent voltage or current sources.

Typically an ideal transformer can be modeled as two dependent sources:


I will use the circuit on the left to model the voltage-sensing transformer (with the voltage source's value changed to V1/n, because the 1-turn winding is the secondary of the voltage-sensing transformer).  And I will use the circuit on the right to model the current-sensing transformer.  But I need to convert each two-dependent source model to one-independent source model.

Let's start with this model showing the Tandem Match's two transformers each replaced with two dependent sources:


The first step -- if I assume that the dependent current source representing the primary of the voltage-sensing transformer introduces negligible current into the transmission line (compared with the current on the line if the Tandem Match were not inserted into the line), then I can replace this source with an open (i.e. representing 0 current).

(Note:  Given that the transmission line's current at the point of measurement due to the load's impedance at that point equals V/Zload', where V is the voltage across the transmission line and Zload' is the load impedance as measured at that point, and given that the current added to the transmission line by the voltage-sense transformer model's dependent current source is V/(2*Zo*(N^2)), then the dependent current source has negligible effect on the transmission line's current if 2*Zo*(N^2) >> Zload'.  (I'll derive this equation later in the post).)

And if I assume that the dependent voltage source representing the primary of the current-sensing transformer introduces a negligible voltage drop into the transmission line (compared to the voltage across the transmission line at the point of measurement if the Tandem Match were not inserted into the line), then I can replace this source with a short (i.e. representing 0 volts).

(Note:  And given that the transmission line's voltage at the point of measurement due to the load's impedance at that point equals I*Zload', where I is the transmission line's current and Zload' is the load impedance as measured at that point, and given that the voltage added into the transmission line  (in series with the load) by the current-sense transformer model's dependent voltage source is I*Zo/(2*N^2), then the dependent voltage source has negligible effect on the transmission line's voltage if Zo/(2N^2) << Zload'.  (I'll derive this equation later in the post).)

The figure below shows the two new models:


(Note that the voltage-sensing transformer's model now represents the correct n:1 turns ratio).

The transformers have now been converted to models each containing a single dependent source.  To convert these two dependent sources to independent sources, recognize that in this application, if these dependent sources have negligible impact on  the current or voltage upon which either depends, then neither affects the other, and thus, for all intents and purposes, these two sources are essentially independent sources, and I can proceed with my analysis using the Principle of Superposition.

I will replace the L1/L2 transformer with a current-source and the L3/L4 transformer with a voltage-source, like this:



To calculate the voltages across R3 and R4, I'm going to use the Principle of Superposition and first calculate the contribution of the voltage-source to the voltages across these two resistors (with the current-source replaced with an open circuit, per the Principle of Superposition.

I will then calculate the contribution of the current-source to the voltages across these two resistors, with the voltage-source replaced with a short.

Let's start with the contribution of the voltage-source to the voltages across R3 and R4.  In the figure below I've replaced the current source with an open circuit and I've defined the voltage polarities across R3 and R4.


Before starting this calculation, let's first assume that R3 = R4 (which, in fact, they do).

Thus, the voltage of the voltage-source is equally divided between the two resistors.  So, the "V" contribution to Vr4 is:

Vr4(V) = (Vfwd+Vref)/(2*N)

Similarly, the "V" contribution to Vr3 is:

Vr3(V) = -(Vfwd+Vref)/(2*N)
Note:
  1. Vr3's minus sign is because the actual polarity is opposite of the polarity I arbitrarily defined in the picture above.
  2. The factor of 2 is because the voltage across each resistor is 1/2 of the voltage-source's value.

Now, let's calculate the contribution of the current-source, "I", to the voltages across R3 and R4.  Per the Principle of Superposition, I first must replace the voltage source with a short, as shown below:


Because R3 = R4, the current divides equally between  the two resistors, and the voltage across each resistor, due to "I", is:

Vr3(I) = -R3*(Ifwd-Iref)/(2*N)

Vr4(I) = -R4*(Ifwd-Iref)/(2*N)

I can now calculate the total voltage across each resistor which, because of the Principle of Superposition, is the sum of the voltages I've just calculated.  Starting with Vr3:

Vr3 = Vr3(V) + Vr3(I)

Substituting, we get:

Vr3 = -(Vfwd+Vref)/(2*N) - R3*(Ifwd-Iref)/(2*N)   (equation 1)

We can do the same for Vr4.  The result is:

Vr4 = (Vfwd+Vref)/(2*N) - R4*(Ifwd-Iref)/(2*N)    (equation 2)

[Sidebar:  Note that equations 1 and 2 allow us to express Vr3 and Vr4 in terms of the line V and I (where V = Va+Vb and I = Ia-Ib, as we defined earlier in this post).  

Vr3 = - (V + I*R3)/(2*N)    (equation 1a)

Vr4 =   (V - I*R4)/(2*N)    (equation 2a)

In other words, Vr3 is an expression in which the voltage-sample and current-sample voltages are summed, while Vr4 is an expression in which the voltage-sample and the current-sample voltages are differenced.]

OK, let's get back to simplifying equations 1 and 2...

Recall that:

Ifwd = Vfwd / Zo
and
Iref = Vref / Zo

where Zo is the characteristic impedance of the transmission line.

If I substitute these into equations 1 and 2, the equations become:

Vr3 = [Vref*(R3 - Zo) - Vfwd*(R3 + Zo)] / (2*Zo*N)
and
 Vr4 = [Vfwd*(Zo - R4) + Vref*(Zo + R4)] / (2*Zo*N)

Still pretty complex.  But we can simplify even further...

We've already defined R3 to be the same value as R4.  Let's also define these values to be the same resistance as the characteristic impedance, Zo, of the transmission line (for example, they could be 50 ohms, if the transmission line were 50 ohm coax).  That is:

R3 = R4 = Zo

This is an important equality.  If R3 and R4 don't equal Zo, the Tandem Match circuit will not correctly calculate forward and reflected voltages.

Substituting this equality into our two equations, the equations reduce to:

Vr3 = -Vfwd/N            (equation 3)
and
Vr4 = Vref/N            (equation 4)

In other words, selecting R3 and R4 to equal Zo (and assuming the voltage drop across L1 and the current through L3 are both negligible), then:
  1. The voltage across Vr3 is solely a function of Vfwd (the signal moving from left-to-right on the transmission line).
  2. The voltage across Vr4 is solely a function of Vref (the signal moving from right-to-left on the transmission line).
Note:  By measuring Vr3 and Vr4, we now know the voltages Vfwd and Vref.  Thus, we also know Forward and Reverse Power:

P(forward) = Pa = (Vfwd^2))/Zo = (Vr3^2)*(N^2)/Zo

P(reverse) = Pb = (Vref^2)/Zo = (Vr4^2)*(N^2)/Zo


Calculating the effect of the dependent voltage and current sources on Transmission Line voltage and current:

The transformers in the Tandem Match each be modeled as two dependent sources:


Earlier in this post I mentioned that if we assume that the two-dependent source models for our transformers have negligible impact upon the transmission line current and voltage, then we can model each transformer as a circuit containing one independent source.

Let's calculate when this assumption is true.  First, let's define the voltage polarities and the current directions based upon the voltage polarities and current directions defined for the transformers:


Therefore, the current-sense transformer's voltage polarities are:


Recognize that the voltage across the secondary of the current sense transformer (with the voltage-sense transformer removed from the circuit) is simply the current of the model's independent current source times R3 and R4 in parallel, which, because R3 = R4 = Zo, means that the secondary voltage is (I/N)*(Zo/2), which can be expressed as I*Zo/(2N).

If the secondary voltage is I*Zo/(2N), then the primary voltage is simply this value divided by N (because it is a 1:N transformer).

Therefore the voltage inserted by the current-sense transformer's primary into the transmission line is:

Vpri = Vsec/N = I*Zo/(2*N^2)

The voltage across the Zload' (the load impedance seen by the transmission line at the point of measurement, assuming Vpri is negligible) is I*Zload'

Therefore, I can state that Vpri is negligible if I*Zo/(2*N^2) is significantly smaller than I*Zload'.  In other words, for  the assumption to be true, the following condition must be met: Zo/(2*N^2) << Zload'.

Next, the voltage-sense transformer (current directions as defined in the transformer circuit, above):

For the voltage-sense transformer, the current added to the transmission line's current by the dependent current source representing the voltage-sense transformer's n-turn primary winding (i.e. Ipri) is the secondary's current divided by N:

Ipri = Isec/N

Isec can be shown to be (if we ignore the effect of the current-sense transformer) (V/N)/(2*Zo), given that R3 in series with R4 are the load of the voltage-source representing the transformer's secondary (ignoring the current-sense transformer). And, because R3 = R4 = Zo and the voltage source representing the secondary has a value of V/N, where V is the transmission line's voltage at the point of measurement.

Therefore:

Ipri = Isec/N = V/(2*Zo*(N^2))

The transmission line's current, if we assume the effect of Ipri is negligible, equals V/Zload'.

Therefore, Ipri is negligible compared to the transmission line's I if V/Zload' is significantly greater than V/(2*Zo*(N^2)), which is met if (2*Zo*(N^2)) >> Zload'.


Analyzing the "Tandem" Directional Coupler in a "Non-Transmission Line" Environment

As stated earlier, this coupler is actually a "lumped-element" device.  That is it's really looking at the voltage and current relationship at, essentially, a single point on the transmission line.  And we can therefore analyze it as a "lumped-element" circuit.  That is, we can analyze its operation as a circuit consisting of a combination of transformers, L's, C's and R's, and no transmission lines or traveling waves.

The drawing below illustrates this concept.  Zload is the load at the coupler's output port.  Let's assume the connection between the coupler and Zload is very short with respect to the wavelength of the signal being measured (it isn't a transmission line):


Note that I haven't shown a driving voltage-source (nor the source-impedance of this source).  It's actually there, connected to the left-hand IN port.  But all I care about is the voltage level, V, at the IN port.


Let's again simplify the analysis by first assuming that the voltage drop across L1 and the current through L3 are both negligible.

Clearly, if there is no voltage drop across L1, then the voltage across Zload is the same as the voltage at the IN port and across L3's N turns.  Let's call this voltage V.
And therefore current I through L1 is simply:

I = V / Zload.

Because L1/L2 and L3/L4 are both transformers, the current through L2 is I/N, and the voltage across L4 is V/N.

We can substitute ideal current and voltage sources for the two transformers (as we did before), and the circuit now looks like:


Using the Principle of Superposition, we can separately analyze the contributions of the voltage source and the current source to Vr3 and Vr4 and then sum these contributions together.

Doing this, we get:

Vr3 = -V/(2*N) - (I*R3)/(2*N)       (equation A)
and
Vr4 = V/(2*N) - (I*R4)/(2*N)        (equation B)

Let's express these in terms of V.  To do this, first recognize that:

I  = V / Zload

Using this relationship, we get:

Vr3 = -V*(R3 + Zload) / (2*N*Zload)      (equation C)
and
Vr4 = V*(Zload - R4) / (2*N*Zload)       (equation D)

Note that V is an unknown, so let's eliminate it from our equations.  To do this, let's rearrange equation C:

V / (2*N*Zload) = -Vr3 / (R3 + Zload)

Substituting this into equation D, we get:

Vr4 = -Vr3*(Zload - R4) / (Zload + R3)   (equation E)

Well, this is interesting.  Note the term:

(Zload - R4) / (Zload + R3) 

Let's say we've designed the coupler for use in a system with a Zo of 50 ohms. So R3 and R4 should be selected to equal the Zo of 50 ohms, and thus:

Vr4 = -Vr3 * (Zload - 50) / (Zload + 50)   (equation F)

(If Vr4 is negative it just means that it is 180 degrees out of phase from Vr3.)

Note the term:

(Zload - 50) / (Zload + 50)

This is the definition of the Reflection Coefficient, Γ (in which 50 is Zo, the characteristic impedance of a transmission line system that this directional coupler might be used in):

Γ = (Zload - Zo) / (Zload + Zo)  

And therefore:

 Γ = -Vr4 / Vr3    (equation G)

So, in other words, if we normalize Vr4 with respect to Vr3, the resulting voltage equals the Reflection Coefficient!

If you are familiar with the inexpensive SWR meters used for Amateur Radio, this is essentially what they do.  You are normalizing the magnitude of Vr4 with respect to the magnitude of Vr3 when you adjust Vr3 to deflect the SWR meter to full-scale before flipping the switch to measure Vr4.  When you do this:
  • Full-scale meter deflection equals a |Γ| of 1.
  • Zero meter deflection equals a |Γ| of 0.
  • And a mid-scale meter deflection equals a  |Γ| of 0.5
(Note:  the SWR Meter is only using the magnitude of Gamma (the magnitude of Gamma is also known as rho).  There is no angle information.)

How does |Γ| relate to SWR?

SWR = (1+|Γ|) / (1-|Γ|)

So if we know the magnitude of Γ (and we do), we therefore know SWR from the above formula.

Remember that the meter, when set to measure Vr4, measures |Γ| over the range from 0 to 1 when the meter is first adjusted to have Vr3 drive it to Full Scale.  We can create an alternate scale, using the above equation, to give us SWR.

|Γ|    SWR
    0     1.00 
 0.1     1.22
 0.2     1.50
 0.3     1.86
 0.4     2.33
 0.5     3.00
 0.6     4.00
 0.7     5.67
 0.8     9.00
 0.9   10.00
 1.0   infinite

Note, for example, that 50% of Full-scale (|Γ| = 0.5) represents an SWR of 3.

Here's a meter and scale I found on the internet (from PY2OHH).  You can see that its SWR markings follow the table above.  E.g. SWR of 3:1 is 50% of the meter's FS.


Summing up:

From the above discussion, it should be evident that we don't need to use concepts of Forward and Reflected waves to understand how the Tandem Match coupler (and SWR meters based on it) operate.

Our typical SWR meter is really just calculating a relationship between the load at its output port (Zload) and its own terminating resistors, R3 and R4.  And this relationship is equivalent to the Reflection Coefficient if R3 and R4 have the same value as Zo of a Transmission Line.

Zload could be a load connected directly to the coupler's "OUT" port with a couple of wires, or it could be the impedance "presented" to the port by a long length of transmission line (an impedance determined, at that point, by the interaction of the Forward and Reflected waves).

The coupler doesn't care "how" the load is connected to its OUT port.  It's just looking at the relation between the voltage across the OUT port and the current through the OUT port.  It doesn't know anything else about the load except for this voltage and current relationship at its OUT port.  For example, if the OUT port happens to be connected to a transmission line, the coupler has no knowledge of the line's Zo. It doesn't even know if there's a transmission line attached, nor that the impedance it sees at its OUT port might be due to the interaction of Forward and Reflected waves.

For this reason, never assume that the meter reading is the actual Reflection Coefficient, Γ, or that the SWR reading is the actual SWR reading of the line.  It might not be.  We are really just measuring the relationship between Zload (as it appears at the OUT port) and the values of R3 and R4.  Only if R3 and R4 equal the actual characteristic impedance, Zo, of the transmission line would we truly be measuring the Reflection Coefficient.


Continuing on...

Here's something else we could do with Vr3 and Vr4:  if we know Vr3 and Vr4, we could also solve for Zload, our unknown load.  Here's how...

Let R3 = R4 = Rt, where Rt is the value we select for our termination resistors at the FWD and REF ports (they could be equal to Zo, but they could be anything else, too.  It only matters that R3 = R4).

Substituting and solving equation E for Zload:

Zload = Rt *(Vr3-Vr4) / (Vr3+Vr4)    (equation H)

Note that these variables and voltages represent complex numbers -- they have both magnitude and phase.  


The above analysis assumes Vsource and Rsource are unknown (often the case if discussing radio transmitters).  But suppose they are known (e.g. if you're using a signal generator).  We can do a similar analysis:

Lumped-element analysis for a known Vsource and Rsource:

Suppose Vsource and Rsource are known (for example, suppose we are using a signal generator with a known 50 ohm source impedance and a known signal level).  Let's rewrite the equations for Vr3 and Vr4 in terms of these new values.  First, we know that

I = Vsource / (Rsource + Zload).

V =  Vsource * (Zload) / (Rsource + Zload).

Substituting these two equations into Equation A and B from above and solving, we get:

Vr3 = -Vsource*(Zload + R3) / (2*N*(Zload + Rsource))
and
Vr4 = Vsource*(Zload - R4) / (2*N*(Zload + Rsource))

If Rsource = R3 = R4, these two equations simplify to:

Vr3 = -Vsource / (2*N)   (equation 3)
and
Vr4 = Vsource*(Zload - Rsource) / (2*N*(Zload + Rsource))   (equation 4)

What do these two equations tell us?

Vr3 will be constant, independent of load.  That is, Vr3 is solely a function of Vsource.
    And, because Γ = (Zload - Zsource) / (Zload+Zsource)  [Note -- this is per Wikipedia.  I prefer to use Zo in lieu of Zsource, but if we assume Zo = Zsource, then they are equivalent.].

    Vr4 = Γ*(Vsource / (2*N))
     
    So Vr4 is directly proportional to a transmission line system's Reflection Coefficient.  Not surprising.  And if we substitute Vsource = -Vr3 * (2*N) (from equation 3) into the equation for Vr4, then

    Vr4 = Γ * (-Vr3)
    or
    Γ = -Vr4 / Vr3

    Which is the same as equation G from our first lumped-element analysis. 



    Links to my Directional Coupler blog posts:

    Notes on the Bruene Coupler, Part 2

    Notes on the Bruene Coupler, Part 1

    Notes on HF Directional Couplers (Tandem Match)

    Building an HF Directional Coupler

    Notes on the Bird Wattmeter

    Notes on the Monimatch

    Notes on the Twin-lead "Twin-Lamp" SWR Indicator

    Calculating Flux Density in Tandem-Match Transformers


    And some related links from my Auto-Tuner posts:

    Auto Tuner, Part 5:  Directional Coupler Design

    Auto Tuner, Part 6:  Notes on Match Detection

    Auto Tuner, Part 8:  The Build, Phase 2 (Integration of Match Detection)

    HF PA, Part 5: T/R Switching and Output Directional Coupler


    Links and Articles for Further Reading:
    • LP-100 Wattmeter -- QEX article by N8LP that contains a good discussion on directional coupler design.
    • If you can access the ARRL's site for QST back issues, you can also look up Bruene's April, 1959 article and Grebenkemper's January, 1987 article (and further Tandem match discussion in January, 1988, and July 1993).
    • US Patent 2285211, Korman, Radio Frequency Wattmeter, Granted June 2, 1942.  Similar to the Tandem Match coupler

    Other notes...

    1.  A note from Dick Benson, W1QG: 
    One sad, but true, reality is to make one of these work well takes more than the usual amount of black magic.

    Strays are everything.   The VNA is indispensable in maximizing performance.  
    (VNA = Vector Network Analyzer.  E.g. HP 8505, 8753, 3577, etc.)


    2.  3/28/2019.  The comment below was made to a different post in this blog.  I thought it worthwhile to add it here.)
    Good day Jeffrey, 

    I recently visited your site on this coupler. I was in the process of presenting a class on reflection coefficient measure and decided to build a coupler for lab work for the students. Accomplished at low frequencies, 1 MHz-30 MHz, it is straight forward to obtain a sufficient Vinc and Vrefl voltage to operate and trigger a low cost scope. 


    As you present in your documentation, the value of GAMMA is the NEGATION of the usual GAMMA definition. Surprise comes about when you attempt to explain the NORMAL action of the reflected voltage across a short, It should be 180 degrees out of phase with the incident voltage so NO voltage is present across the short. An open circuit is exactly opposite and Vinc should be in phase with Vref. However, for both cases it is the exact opposite for this coupler. 

    I think this would be a worthwhile item to mention in the blog, particularly when one decides to build the coupler and actually go in there and measure the PHASE of the voltages; Vrefl and Vinc. A bit of head scratching at first! 

    Thanks, Alan Victor, W4AMV
    This is a good point: the circuit topology as described above results in Vfwd being proportional to -Vr3 (per the mathematical derivation), rather than +Vr3.  I will note that if it is important to the user that Vfwd be the same polarity as Vr3, this could probably be accomplished by changing the phase of one of the transformer windings (I will leave the analysis to the reader).  


    Caveats:

    These notes are meant to aid the reader in understanding how directional couplers work.  But this is not a rigorous analysis.  I've made a number of assumptions to simplify the math.  For example, the two transformers within the Tandem Match coupler are assumed to be ideal.  In the real world, they are not.  A complete analysis would take into account, for example, their inductances and the mutual coupling between primaries and secondaries.

    Finally, I could easily have made a mistake in my interpretations and/or analysis.  So take everything with a grain of salt.  If there's something here that doesn't look right to you, please feel free to email me.